Pump
|
|
Suction pressure across
|
max. -0.4 bar to 0.5 bar
|
the suction connection
|
Operating pressure (oil side)
|
max. 6 bar
|
Medium (oil side)
|
Mineral oil to DIN 51524 Part 1 and Part 2
|
Temperature range (oil side)
|
10 ?C to 80 ?C
|
Permissible contamination
|
≤ NAS12 or ISO4406: 22/21/18
|
(oil side)
|
Max. viscosity
|
see viscosity-temperature graph
|
Drive
|
|
Motor
|
Three-phase electric motor
|
|
Insulation class: F
|
|
Protection class: IP55
|
Speed
|
1,500 / 1,800 1/min (50/60 Hz)
|
Heat exchanger
|
Heat exchanger connections:
|
Female thread (max. tightening torque 160 Nm)
|
|
The pipes must be connected so that the connections are stress-free.
|
|
Linear expansion and vibrations from the pipes to the heat exchanger
|
|
must be avoided.
|
Medium (water side):
|
Water glycol (HFC)
|
|
Water
|
|
Oils
|
Temperature range (water side)
|
5 ?C to 60 ?C
|
Operating pressure (water side):
|
max. 30 bar
|
Permissible contamination
|
The level of particles in suspension should be less than 10 mg/l.
|
(water side)
|
Particle size <0.6 mm (spherical)
|
|
Thread-like particles cause a rapid increase in pressure losses.
|
Water quality
|
The following ions are not corrosive under normal conditions:
|
|
phosphate, nitrate, nitrite, manganese, sodium and potassium
|
|
also see table on water quality
|